- Products
- Insulation monitoring devices for safety in the IT system

ISOMETER® iso685…
- Predefined measurement profiles
- Reliable measurement of insulation resistance, voltage, capacitance and frequency
- Integrated web server
- Modbus TCP/RTU
- History memory
The ISOMETER® is an insulation monitoring devices in accordance with IEC 61557-8 for IT systems. The devices are universally applicable in AC, 3(N)AC, AC/DC and DC systems. AC systems may include extensive DC-supplied loads (such as rectifiers, inverters, variablespeed drives).
Device variants
iso685-D: The device variant iso685-D features a high-resolution graphic LC display and operating controls for direct operation of the device functions.
iso685-S: The device variant iso685-S is operated via the detached operating unit FP200.
Option "W": The ISOMETER®s with and without integrated display are available for extreme climatic and mechanical conditions.
- Products
- Products
- Features
- Applications
- Accessories
- Ordering information
- Downloads
- ISOMETER® for IT AC systems with galvanically connected rectifiers or inverters and for IT DC systems (IT = unearthed systems).
- Nominal system voltage Un expandable via coupling devices
- Automatic adaptation to the existing system leakage capacitance.
- Combination of AMPPlus and other profilespecific measurement methods.
- Two separately adjustable response value ranges of 1 kΩ…10 MΩ for alarm 1 and alarm 2
- High-resolution graphic LC display for excellent readability and recording of the device status.
- Connection monitoring (monitoring of the measuring lines).
- Automatic device self test.
- Graphical representation of the insulation resistance over time (isoGraph)
- History memory with real-time clock (buffer for three days) for storing 1023 alarm messages with date and time.
- Current and voltage output 0(4)…20 mA, 0…400 μA, 0…10 V, 2…10 V (galvanically separated) which is analogous to the measured insulation value of the system.
- Freely programmable digital inputs and outputs.
- Remote setting via the Internet or Intranet (Webserver/Option: COMTRAXX® Gateway).
- Worldwide remote diagnosis via Internet.
- RS-485/BS (Bender sensor bus) for communication with other Bender devices
- BCOM, Modbus TCP/RTU and web server
- AC, DC or AC/DC main circuits
- AC/DC main circuits with directly connected DC components, such as rectifiers, converters, variable-speed drives
- UPS systems, battery systems
- Heaters with phase control
- Systems including switched-mode power supplies
- IT systems with high leakage capacitances
Mandatory accessories for ISOMETER® iso685…
Type designation | Art. No. |
---|---|
A set of screw terminals* | B91067901 |
A set of push-wire terminals | B91067902 |
Enclosure accessories (terminal cover, 2 mounting clips)* | B91067903 |
Transparent cover 144x72 (IP65) for FP200** | B98060005 |
** If the “transparent front cover 144x72 (IP65)” is used, the cutout in the control cabinet must be increased in height from 66 mm to 68 mm (+ 0.7 / -0 mm).
Optional accessories for ISOMETER® iso685…
Type designation | Type | Art. No. |
---|---|---|
Coupling devices | AGH150W-4 AGH204S-4 AGH520S AGH676S-4 | B98018006 B914013 B913033 B913055 |
Variants of ISOMETER® iso685…
Type | Nominal system voltage range Un | Supply voltage US | Display | Option W* | Art. No. |
---|---|---|---|---|---|
iso685-D | AC 0…690 V; 1…460 Hz / DC 0…1000 V | AC 24…240 V; 50…400 Hz / DC 24…240 V | integrated | – | B91067010 |
iso685W-D* | AC 0…690 V; 1…460 Hz / DC 0…1000 V | AC 24…240 V; 50…400 Hz / DC 24…240 V | integrated | -40…+70°C, 3K5, 3M7 | B91067010W |
iso685-S + FP200 | AC 0…690 V; 1…460 Hz / DC 0…1000 V | AC 24…240 V; 50…400 Hz / DC 24…240 V | detached | – | B91067210 |
iso685W-S + FP200* | AC 0…690 V; 1…460 Hz / DC 0…1000 V | AC 24…240 V; 50…400 Hz / DC 24…240 V | detached | -40…+70°C, 3K5, 3M7 | B91067210W |
Device variants
iso685-D: This device variant ISOMETER® iso685-D features a high-resolution graphic LC display and operating controls for direct operation of the device functions. It cannot be combined with an FP200.
iso685-S: This device variant ISOMETER® iso685-S features neither a display nor operating controls. It can only be used in combination with the FP200 and it is operated via this front panel.
Option "W": The ISOMETER®s with and without integrated display are available with option „W“ for extreme climatic and mechanical conditions (ISOMETER® iso685W-D and iso685W-S).
Downloads for ISOMETER® iso685…
Category | Product | Language | Size | Download |
---|